PT100 & PT1000 RTD Resistance Calculator
Exact Callendar–Van Dusen Ohms ↔ °C / °F solver for PT100 and PT1000 sensors with 2-wire cable error diagnostics and Class AA / A / B tolerance bands.
On a PT100, just 1.0 Ω of uncompensated 2-wire cable resistance adds ~+2.6 °C error.
IEC 60751 Callendar–Van Dusen Formula
Quick field rule of thumb: disconnect the RTD from the PLC terminal block before measuring ohms with a handheld multimeter, otherwise the PLC card's excitation current will skew your reading.
Frequently Asked Questions
What is the resistance of a PT100 sensor at 0 °C, 25 °C, and 100 °C?+
Under IEC 60751 (alpha = 0.00385 Ω/Ω/°C), a PT100 RTD measures exactly 100.00 Ω at 0 °C, 109.73 Ω at 25 °C, and 138.51 Ω at 100 °C. A PT1000 sensor scales these resistances by 10x (1000.0 Ω at 0 °C and 1385.1 Ω at 100 °C).
Why does a 2-wire PT100 read high in a PLC RTD input module?+
A PT100 changes by only ~0.385 Ω per °C. In a 2-wire hookup, copper lead-wire resistance adds directly in series with the sensing element—just 1.0 Ω of cable loop resistance creates a +2.6 °C high reading. Use 3-wire RTDs (matched leads) or 4-wire RTDs to cancel lead resistance.
What is the Callendar–Van Dusen equation used by PLC RTD cards?+
For temperatures 0 °C to 850 °C, R(T) = R0 * (1 + A*T + B*T²). Below 0 °C (down to -200 °C), a fourth-order term is added: R(T) = R0 * [1 + A*T + B*T² + C*(T - 100)*T³], where A = 3.9083e-3, B = -5.775e-7, and C = -4.183e-12.
What is the difference between Class A and Class B PT100 accuracy?+
At 0 °C, IEC 60751 Class A tolerance is ±0.15 °C (±(0.15 + 0.002|T|)), while Class B tolerance is ±0.30 °C (±(0.30 + 0.005|T|)). Class AA (1/3 DIN) tightens this to ±0.10 °C at 0 °C.
Complete PLC & Industrial Automation Calculator Suite
Bitwise & Data Formats
Simulate 16-bit INT and 32-bit DINT Masked Move instructions bit-by-bit with clickable mask gates and Structured Text output.
Decode or encode two 16-bit Holding Registers across all 4 endian byte orders (ABCD, CDAB, BADC, DCBA) for 32-bit REAL floats.
Convert between 16/32-bit Binary-Coded Decimal (BCD) thumbwheel words and integer values with invalid A–F nibble fault detection.
Analog I/O & Sensors
Convert raw ADC counts (4000–20000, 6241–31206, 0–27648) and 4–20 mA signals into engineering units with 5-point calibration tables.
Bidirectional Callendar–Van Dusen (°C/°F ↔ Ohms) calculator for PT100 and PT1000 RTDs with Class AA, A, and B tolerance bands.
Convert thermocouple millivolt (mV) readings to process temperature and back with live Cold Junction Compensation (CJC).
Estimate cabinet temperature rise, conductive heat transfer, required cooling fan airflow (CFM), and AC capacity (BTU/hr) for enclosures.
Fieldbus, Motion & Control
Compute polynomial 0xA001 CRC-16 checksums in Little-Endian Lo-Byte / Hi-Byte wire order and validate captured RS-485 frames.
Calculate maximum RS-485 trunk length, Modbus RTU 3.5-character silent interval (t3.5), frame duration, and max polling rate.
Compute synchronous speed, motor slip %, output shaft RPM after gearbox reduction, and target VFD command frequency in Hz.
Verify PLC High-Speed Counter (HSC) kHz input limits from encoder PPR, 1x/2x/4x quadrature decoding, shaft RPM, and linear travel.
Convert Independent (Kp, Ki, Kd) vs. ISA Dependent (Kc, Ti, Td) PID gains and compute FOPDT / Ultimate Gain starting parameters.