FIELDBUS · TIA/EIA-485 & MODBUS RTU

RS-485 Baud Rate, Cable Length & Timing Calculator

Size RS-485 serial trunks, verify Modbus t3.5 inter-frame silence, check 32-Unit-Load limits, and estimate max slave polling throughput.

RS-485 Serial Trunk & Frame Parameters

Select baud rate, character framing, and Modbus RTU packet size

Baud Rate (bps)
Max Recommended Trunk Length
1200 m (3937 ft)
120 Ω end-of-line resistors recommended past ~1042 m
Modbus t3.5 Silent Interval
2.005 ms
Raw 3.5 chars: 2.005 ms · t1.5: 0.859 ms
1 Character Duration (11 bits):572.9 µs (0.573 ms)
Master Request Wire Time:4.58 ms
Slave Response Wire Time:14.32 ms
Total Poll Round-Trip Cycle:27.92 ms (~35.8 polls/sec)
Bus Electrical Loading: 3.00 / 32.0 Unit Loads used (Within limit — up to 128 devices supported without a repeater.)

Field Wiring Checklist for Reliable RS-485

  • Use dedicated 120 Ω characteristic impedance shielded twisted pair (not standard unshielded CAT5 power-tray cable for long VFD runs).
  • Always connect the 3rd reference wire (Signal Common / 0V) between transceivers so common-mode voltage stays within −7V to +12V.
  • Ground the cable shield drain wire at one end only (typically the PLC cabinet earth bar) to prevent ground-loop currents.

Frequently Asked Questions

What is the maximum cable length for RS-485 at 9600 or 19200 baud?+

Under TIA/EIA-485 guidelines using low-capacitance 120 Ω shielded twisted-pair cable (such as Belden 3105A or 9841), the maximum single-segment trunk length up to 90–100 kbps is 1,200 meters (approximately 4,000 feet) without an isolated repeater.

How is the Modbus RTU 3.5-character silent interval (t3.5) calculated?+

At 19,200 bps and below, t3.5 = 3.5 * (bits_per_char / baud_rate). For standard 11-bit framing (8E1) at 9600 bps, t3.5 = 4.010 ms. Above 19,200 bps, the Modbus over Serial Line specification fixes t1.5 at 0.750 ms and t3.5 at 1.750 ms to reduce CPU timer overhead.

Where should 120-ohm RS-485 termination resistors be installed?+

Install exactly two 120 Ω resistors—one at each physical extreme end of the linear daisy-chain bus (across A/B or D+/D−). Never place termination resistors on intermediate drops or wire RS-485 in a star topology.

How many Modbus RTU slaves can sit on one RS-485 segment?+

TIA-485 specifies 32 Unit Loads (UL) per segment. Legacy 1-UL transceivers allow 32 total devices (1 master + 31 slaves), whereas modern 1/4-UL and 1/8-UL transceivers support up to 128 or 247 addressable Modbus slaves on a single electrical trunk.