RS-485 Baud Rate, Cable Length & Timing Calculator
Size RS-485 serial trunks, verify Modbus t3.5 inter-frame silence, check 32-Unit-Load limits, and estimate max slave polling throughput.
RS-485 Serial Trunk & Frame Parameters
Select baud rate, character framing, and Modbus RTU packet size
Field Wiring Checklist for Reliable RS-485
- Use dedicated 120 Ω characteristic impedance shielded twisted pair (not standard unshielded CAT5 power-tray cable for long VFD runs).
- Always connect the 3rd reference wire (Signal Common / 0V) between transceivers so common-mode voltage stays within −7V to +12V.
- Ground the cable shield drain wire at one end only (typically the PLC cabinet earth bar) to prevent ground-loop currents.
Frequently Asked Questions
What is the maximum cable length for RS-485 at 9600 or 19200 baud?+
Under TIA/EIA-485 guidelines using low-capacitance 120 Ω shielded twisted-pair cable (such as Belden 3105A or 9841), the maximum single-segment trunk length up to 90–100 kbps is 1,200 meters (approximately 4,000 feet) without an isolated repeater.
How is the Modbus RTU 3.5-character silent interval (t3.5) calculated?+
At 19,200 bps and below, t3.5 = 3.5 * (bits_per_char / baud_rate). For standard 11-bit framing (8E1) at 9600 bps, t3.5 = 4.010 ms. Above 19,200 bps, the Modbus over Serial Line specification fixes t1.5 at 0.750 ms and t3.5 at 1.750 ms to reduce CPU timer overhead.
Where should 120-ohm RS-485 termination resistors be installed?+
Install exactly two 120 Ω resistors—one at each physical extreme end of the linear daisy-chain bus (across A/B or D+/D−). Never place termination resistors on intermediate drops or wire RS-485 in a star topology.
How many Modbus RTU slaves can sit on one RS-485 segment?+
TIA-485 specifies 32 Unit Loads (UL) per segment. Legacy 1-UL transceivers allow 32 total devices (1 master + 31 slaves), whereas modern 1/4-UL and 1/8-UL transceivers support up to 128 or 247 addressable Modbus slaves on a single electrical trunk.
Complete PLC & Industrial Automation Calculator Suite
Bitwise & Data Formats
Simulate 16-bit INT and 32-bit DINT Masked Move instructions bit-by-bit with clickable mask gates and Structured Text output.
Decode or encode two 16-bit Holding Registers across all 4 endian byte orders (ABCD, CDAB, BADC, DCBA) for 32-bit REAL floats.
Convert between 16/32-bit Binary-Coded Decimal (BCD) thumbwheel words and integer values with invalid A–F nibble fault detection.
Analog I/O & Sensors
Convert raw ADC counts (4000–20000, 6241–31206, 0–27648) and 4–20 mA signals into engineering units with 5-point calibration tables.
Bidirectional Callendar–Van Dusen (°C/°F ↔ Ohms) calculator for PT100 and PT1000 RTDs with Class AA, A, and B tolerance bands.
Convert thermocouple millivolt (mV) readings to process temperature and back with live Cold Junction Compensation (CJC).
Estimate cabinet temperature rise, conductive heat transfer, required cooling fan airflow (CFM), and AC capacity (BTU/hr) for enclosures.
Fieldbus, Motion & Control
Compute polynomial 0xA001 CRC-16 checksums in Little-Endian Lo-Byte / Hi-Byte wire order and validate captured RS-485 frames.
Calculate maximum RS-485 trunk length, Modbus RTU 3.5-character silent interval (t3.5), frame duration, and max polling rate.
Compute synchronous speed, motor slip %, output shaft RPM after gearbox reduction, and target VFD command frequency in Hz.
Verify PLC High-Speed Counter (HSC) kHz input limits from encoder PPR, 1x/2x/4x quadrature decoding, shaft RPM, and linear travel.
Convert Independent (Kp, Ki, Kd) vs. ISA Dependent (Kc, Ti, Td) PID gains and compute FOPDT / Ultimate Gain starting parameters.